BASIC SYSTEM DESIGN CRITERIA |
 |
Built in accordance with BS 5839 Pt 8; BS 7443 and Customer Specification
|
 |
Immune from and shall not radiate signals exceeding limits of BS EN 50081, BS EN 50082 and
BS EN 55014
|
 |
Terminology for characteristics and measurement techniques of Sound System Equipment is in accordance
with BS 6840; IEC 268
|
 |
Fully duplicated systems monitored by central microprocessor controlling all tests, collating data,
analyzing results and displaying error codes
|
 |
Interconnection from Fire & Gas, Process Control, Shutdown systems etc will be monitored for open and
short circuit
|
 |
Main Control Systems will be built using 19” Rack equipment
|
 |
Access Panels can either be 19” rack, wall mounted or custom built to suit site requirements
|
 |
Power Supply 110 - 250V ac and 24V dc with battery backup, all inside main control equipment
|
 |
Access Panel Circuits will be fully duplicated and fault monitored
|
 |
System surveillance design will ensure full security of complete emergency control and audio paths
|
 |
Integrity, fault monitoring and warning shall be in accordance with BS 5839 Pt 8 1998
|
 |
All Critical Control and Audio Paths from the external initiation sources, secure access unit/s and
emergency message / tone units to the field mounted horns / speakers will be fully monitored
|
 |
The monitoring system will show all faults using a 7 segment LED display and can provide facilities for
remote indication of these signals if required.
|
 |
All monitoring of audio paths will be inaudible
|
 |
Failure of any card or module required to maintain system integrity shall be
clearly identified and the system shall provide for automatic substitution
|
 |
Beacon monitoring circuits for continuity checking
|
| |
Additional options |
 |
PABX Interface |
 |
Party Page System Interface |